| GMT

Cobalt Data Centre Campus@Newcastle NE28 9NZ
internal images of Cobalt Date Centre
cobalt data centre specification

The fitout of the scheme can be designed up to a Tier IV specification to accommodate any occupiers requirement. Our standard Tier III (N+1) offering is detailed here;

Specification includes:

Power

  • Two diverse 40MVA supplies from SSE Switchrooms fed directly from 275KV 40/60MVA National Grid super grid transformers
  • Potential to upgrade to two 60MVA supplies

Building shell

  • 4,262 sq m net technical area
  • Four autonomous data halls @ 1,066 sq m net technical each
  • Seperate secure CRAC corridor for each hall
  • 6000mm data hall slab to soffit height
  • Steel framed building
  • Roof construction; Aluminium Standing Steam over Concrete Slab at 3°

Data Centre

  • Data hall floor loading:
    • Imposed loading 12kN/m² UDL
    • Ceiling and services 2.4kN/m² UDL
    • Raised floor access 0.6kN/m² UDL
    • 800mm clear raised floor void
  • 800mm clear raised floor void
  • Dedicated unpacking and IT assembly areas
  • Dedicated store rooms

Offices

  • Cat A Offices - 275 sq m
    • Naturally Ventilated
    • Full height glazing
    • Sub divisible
    • Raised floor
    • Shared meeting rooms
    • Shared amenities
    • Shared goods/passenger lift
  • BREEAM ‘Excellent’ rating
  • Scheduled completion 2010
building cutaway illustration
data hall cutaway illustration

Data Hall with racking